检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:冯宇 吴士普 吴细秀[2] 刘衍 龙国华 王磊 李超[2] 周帆[2] 张圆圆 FENG Yu;WU Shipu;WU Xixiu;LIU Yan;LONG Guohua;WANG Lei;LI Chao;ZHOU Fan;ZHANG Yuanyuan(China Electric Power Research Institution Co.,Ltd.,Wuhan 430074,China;WuHan University of Technology,Wuhan 430070,China;Jiangxi Electric Power Research Institution Co.,Ltd.,Nanchang 330096,China)
机构地区:[1]中国电力科学研究院有限公司,武汉430074 [2]武汉理工大学,武汉430070 [3]国网江西省电力有限公司电力科学研究院,南昌330096
出 处:《高压电器》2019年第2期31-38,共8页High Voltage Apparatus
基 金:国家电网公司科技项目(GY71-16-006)~~
摘 要:为验证高频过电压抑制导线(以下简称抑制导线)对VFTO抑制效果,在某550 kV GIS试验平台上开展了VFTO抑制验证试验。为开展试验,依据IEC 62271?102—2013标准对试验平台的尺寸进行了优化设计。依据GIS的工作工况,设计了加交流、直流、隔离开关分闸、合闸等试验条件。从VFTO的幅值、持续时间、击穿次数和频率成分方面对安装抑制导线前后的试验结果进行了总结分析。试验结果表明:VFTO最高幅值可从安装前2.42p.u.下降为1.49p.u.;幅值抑制比最大可达52.94%,最小也有22.22%;安装抑制导线后,全波击穿次数可从13次减少到5次,持续时间从7个工频周波减少到2.5个工频周波;同时试验结果揭示抑制导线对VFTO的高频成分抑制效果明显。上述结果表明:高频过电压抑制导线法对VFTO具有很好的抑制效果,是一种极具工程应用前景的方法。In order to verify the VFTO suppression effect of the restraining busbar,the VFTO suppression verification test was carried out on a 550 kV GIS test platform.In order to carry out the test,the dimensions of the test platform were optimized according to the IEC 62271-102-2013 standard.According to the working conditions of GIS,the test conditions of AC,DC,disconnector opening and closing are designed.From the aspect of VFTO,the duration,the number of breakdowns and the frequency components,the test results before and after the installation of the restraining busbar are summarized and analyzed.The test results show that the maximum amplitude of VFTO can be reduced from 2.42 p.u.to 1.49 p.u.before installation;the amplitude suppression ratio can reach up to 52.94%,and the minimum is also 22.22%;after installing the restraining busbar,the number of full-wave breakdown can be reduced from 13 times to 5 times,the duration is reduced from 7 power frequency cycles to 2.5 power frequency cycles;at the same time,the test results reveale that the restraining busbar has a significant effect on the high frequency component suppression of VFTO.The verification test shows that the restraining busbar has a good suppression effect on VFTO,and it is a method with great engineering application prospects.
关 键 词:VFTO GIS 抑制 高频过电压抑制导线 击穿次数 试验研究
分 类 号:TM63[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.15