供热机组测功法甩负荷试验  

Load-rejection testing of heat supply turbo-generator unit using dynamometry

在线阅读下载全文

作  者:金生祥[1] 伍小林[1] 张志勇[1] 仝茂峰 王法伦 

机构地区:[1]华北电力科学研究院有限责任公司,北京100045 [2]北京京能热电股份有限公司,北京100041

出  处:《中国电力》2002年第3期6-9,共4页Electric Power

摘  要:机组在供热工况下进行常规法甩负荷有很多风险,一般极少采用。通过对北京京能热电股份有限公司供热机组进行供热工况测功法甩负荷试验,介绍供热机组供热工况测功法甩负荷试验方法,对测功法换算飞升曲线的误差采用简易可行的修正,从理论上对供热机组供热工况测功法和常规法甩负荷时转速飞升作了对比性分析,为供热机组供热工况常规法甩负荷试验奠定了理论和实践上的依据。Conventional load-rejection testing is seldom used for heat supply turbo-generator unit in heat supply condition,since there are risks existing during testing.With the load-rejection testing using dynamometry carried out on the No.3heat supply turbo-generator unit of Beijing Jingneng Cogeneration Corp.in heat supply condition as example,this article introduces the load-rejection testing method of heat supply unit in heat supply condition using dynamometry.The error of conversion from dynamometry to flying-up curve is corrected using practical simplified method,the contrast-analysis of rotating speed flying-up during load-rejection testing of heat supply unit in heat supply condition using dynamometry and using conventional method is carried out theoretically,which lays the theoretical and practical basis for load-rejection testing of heat supply unit in heat supply condition using conventional method.

关 键 词:汽轮机 供热机组 测功法 甩负荷试验 

分 类 号:TK267[动力工程及工程热物理—动力机械及工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象