检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]山东大学,济南250061 [2]齐鲁石化公司腈纶厂,淄博255040
出 处:《电力电子技术》2002年第3期7-8,共2页Power Electronics
摘 要:根据变电站的运行特点 ,采用最先进的无功调节判据 ,研制了变电站电压无功自动控制装置 ,以实现变电站电压无功的优化控制。该装置能在电压合格、无功基本平衡时 ,使有载调压变压器的分接开关次数和并联补尝电容器的投切次数降至最少 ,从而大大提高变压器有载分接开关的使用寿命并使变电站电压合格率达到 10 0 % ,线损降低 2 0According to substation running properties and using the most advanced reactive regulating criteria, a substation voltage and reactive power automatic control equipment for realizing optimization control is developed. At the balanced reactive power and the qualified voltage the equipment can ensure minimum operation times of transformer tap and parallely compensate the capacitor switch.The lifetime of transformer taps and capactitor switches increases largely, and substation voltage qualification rate is reached to 100%,as well as the line loss is reduced about 20%.
分 类 号:TM714.3[电气工程—电力系统及自动化] TM63