检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华北电力大学,河北保定071000
出 处:《电工电气》2014年第7期8-12,共5页Electrotechnics Electric
基 金:国家电网公司科技项目(XT71-12-009)
摘 要:针对发电机自动励磁调节器中伏赫兹限制曲线的整定与发变组中过激磁保护曲线整定配合不尽合理的现象,分析了两者之间的动作特性以及过激磁保护经常配置的两套方案,根据相关理论和它们的功能推导出伏赫兹限制应优先于过激磁保护动作,归纳出了伏赫兹限制与定时限过激磁保护、反时限过激磁保护之间配合整定的原则。结合工程实例进行分析,指出在配合整定合理的情况下要考虑两者之间留有合理的级差来更好地保证发电机的安全。Aiming at unreasonable coordination issues of V/Hz limit curves setting in automatic voltage regulator of generator and over excitation protection curves setting in transformer unit, this paper analyzed the action features between the two settings and two plans of over excitation protection normal disposition. According to the related theory and their functions, this paper deduced that V/Hz limit should have priority before over excitation action, generalizing the coordination setting principle among V/Hz limit, time limit over excitation protection and inverse time limit over excitation protection. The engineering practical example analysis shows that under the conditions of reasonable coordination setting, a reasonable grade difference between the two settings should be kept to ensure the safety of generator better.