590互感器校验仪在长母线GIS现场测试中的局限性  被引量:7

The Limitation of Model 590 Transformer Testers in the long-bus GIS Substation Field Test

在线阅读下载全文

作  者:刘罡[1] 曾辉明[1] 程力[2] 佟志欣 房琛 

机构地区:[1]国网辽宁省电力有限公司电力科学研究院,辽宁沈阳110006 [2]太平湾发电厂,辽宁丹东118000 [3]华晨宝马汽车有限公司,辽宁沈阳110044 [4]大连电力建筑工程公司,辽宁大连116021

出  处:《东北电力技术》2014年第5期52-55,共4页Northeast Electric Power Technology

摘  要:近年来,随着GIS变电站的普及,590系列互感器校验仪越来越多地被使用。在用590系列互感器校验仪进行GIS现场试验中,屡屡出现了试验结果超差的问题。为分析其原因,在辽宁某GIS现场和非GIS现场提出比对试验。通过原理分析,得出试验结果超差的根本原因,最后得出590系列互感器校验仪在长母线管GIS现场慎用的结论。With the popularity of GIS substations, Model 590 transfornler testers are commonly used. However, the test resuh is of- ten out of range when experiment by Model 590 transformer testers in the GIS substation is done. In order to solve the proble,n, com- parison test in GIS substation and non-GIS substation is caaried out. Through the analysis of the principle the root cause is found that Model 590 transformer testers should be used with caution in the long-bus tube substation.

关 键 词:GIS 590互感器校验仪 电力互感器 长母线管 

分 类 号:TM45[电气工程—电器]

 