摘  要:For multiple grid-connected inverters with active filter function,it makes sense to regulate every unit to output maximum active power from photovoltaic arrays,as well as eliminate the harmonic due to the non-linear loads connected to the electric networks.Naturally,a centralized control coordination strategy was proposed for the purpose of high facility utilization,good harmonic compensation ability and unwanted overcompensation condition.Based on a vector decoupling control scheme and generalized instantaneous reactive power theory,the solution was to allocate the harmonic eliminating task for every inverter according to the instantaneous power margin of each.The grid current always keeps sinusoidal in spite of non-linear load change and output active power change for any inverter.The simulation results validate the efficacy of the proposed coordination strategy.For multiple grid-connected inverters with active filter function, it makes sense to regulate every unit to output maximum active power from photovoltaic arrays, as well as eliminate the harmonic due to the non-linear loads connected to the electric networks. Naturally, a centralized control coordination strategy was proposed for the purpose of high facility utilization, good harmonic compensation ability and unwanted overcompensation condition. Based on a vector decoupling control scheme and generalized instantaneous reactive power theory, the solution was to allocate the harmonic eliminating task for every inverter according to the instantaneous power margin of each. The grid current always keeps sinusoidal in spite of non-linear load change and output active power change for any inverter. The simulation results validate the efficacy of the proposed coordination strategy.

关 键 词:active filter HARMONICS grid-connected inverter decoupling control COORDINATION 

分 类 号:TM464[电气工程—电器]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象