LiBr溶液除湿系统再生器性能正交试验研究  被引量:7

Orthogonal Experiment Investigation on Regenerator Performance of LiBr-liquid Desiccant System

在线阅读下载全文

作  者:黄志甲[1] 王玉忠[1] 周立宁[1] 

机构地区:[1]安徽工业大学,安徽马鞍山243002

出  处:《流体机械》2014年第8期69-72,6,共5页Fluid Machinery

基  金:安徽省自然科学基金项目(11040606M110)

摘  要:再生器是溶液除湿系统的重要传热传质部件。本文设计了正交试验,对入口溶液温度、液气比、入口溶液浓度、入口溶液流量这4个因素对再生性能的影响程度进行了试验研究,正交试验表明,各因素对再生性能的影响程度依次为入口溶液温度、液气比、入口溶液浓度、入口溶液流量,其中入口溶液温度对再生率结果影响最大。The regenerator is the important heat and mass transfer components in liquid desiccant system. Through orthogonal experiment design,experimentally studies influences of desiccant inlet temperature,inlet liquid-air ratio,desiccant inlet concentration,and desiccant flow rate on the regeneration performance. Orthogonal experimental analysis show that the sequencing of various factors in the influence on the regeneration performance is the desiccant inlet temperature,liquid-air ratio,desiccant inlet concentration,inlet desiccant flow rate,desiccant inlet temperature have a significant impact on the regeneration rate.

关 键 词:溶液除湿 再生器 正交试验 