检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:杨涛
出 处:《贵州电力技术》2014年第9期7-9,共3页Guizhou Electric Power Technology
摘 要:当断路器发生单相重燃时,电容器组中性点会产生高频振荡,出现较大的过电压,这一过电压传递到电容器上,导致电容器对地也出现较高过电压,而电容器极间无过电压产生。当断路器发生两相重燃时,除了中性点和电容器对地出现过电压外,电容器极间也会出现过电压。由于并联电容器开断时间和重燃时间存在随机性,并不总是在最严重的时刻发生,因此实际的过电压较仿真结果要小。Neutral point of capacitor bank would produce high-frequency oscillation and appear larger overvohage when the circuit breaker in single-phase rekindle. Overvoltage in capacitor to ground was too high, and the capacitor electrode did not produce overvoltage. The capacitor electrode would produce overvoltage when the circuit breaker in two-phase rekindle. The breaking time and rekindle time of the parallel capacitor were random, the realistic overvohage was smaller than simulation result.
关 键 词:真空断路器 并联电容器 重燃过电压 电磁暂态程序(EMTP)