上海某办公楼THIC空调系统节能效果分析  被引量:1

Analysis of Energy Saving Effect of THIC Air Conditioning System in an Office Building in Shanghai

在线阅读下载全文

作  者:张智文[1] 张启林[1] 康丽艳[1] 王彦禹 

机构地区:[1]上海海事大学,上海201306

出  处:《制冷》2015年第1期85-89,共5页Refrigeration

摘  要:本文通过分析上海某办公楼THIC空调系统(温湿度独立控制空调系统)的能耗比例,指出对于THIC空调系统中处理显热的系统,因冷水机组随蒸发温度的提高使COP值提高而节能;对于THIC空调系统中处理潜热的系统,因溶液再生能耗有可能抵消甚至超过处理显热系统节约的能耗,从而会造成THIC系统相比于常规系统不节能的后果。Paper through analysis Shanghai a Office THIC air conditioning system ( temperature humidity independ-ent control air conditioning system) of energy proportions, pointed out that for THIC air conditioning system in the processing explicit hot of system, due to cold water unit with evaporation temperature of improve makes COP value improve and energy; for THIC air conditioning system in the processing latent heat of system, due to solution regen-eration energy has may offset even over processing explicit hot system save of energy, thus will caused the THIC sys-tem compared to the general system not energy.

关 键 词:THIC空调系统 新风处理 节能 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]

 