基于相关系数分析有载分接开关内漏故障的处理  

Dispose of internal leakage fauit of on-load tap changer based on correlation coefficient analysis

在线阅读下载全文

作  者:李诗勇[1] 薛静[1] 施艳[1] 杨俊秋[1] 

机构地区:[1]贵阳供电局,贵州贵阳550081

出  处:《贵州电力技术》2015年第6期39-40,84,共3页Guizhou Electric Power Technology

摘  要:色谱分析试验发现变压器油中溶解气体含量超注意值,通过对变压器本体与分接开关油中特征气体含量的相关系数进行计算分析,判断出有载分接开关油箱存在内漏故障,停电检查证实了分析判断的准确性,总结出类似故障的分析判断经验。It was identified in the chromatographic analysis test that content of dissolved gas in transformer oil exceeded attention valueand it was concluded that the on-load tap changer oil tank had an internal leak based on calculation of and analysis on correlationcoefficient of characteristic gas content in transformer proper and tap changer oil, accuracy of which were verified in the black-outinspection. This has been gained as the experience to analyze and determine similar failures.

关 键 词:相关系数 变压器 有裁分接开关 内漏 色谱分析 故障处理 

分 类 号:TM403.4[电气工程—电器]

 