某水电站机组主轴密封供水中断原因分析及处理  被引量:2

Cause analysis of water supply break- off of main shaft seal of a hydropower plant unit in Vietnam and its treatment

在线阅读下载全文

作  者:胡雄峰[1] 郑应霞[1] 丁国平[1] 邓新星[1] 

机构地区:[1]中国电建集团华东勘测设计研究院有限公司,浙江杭州310014

出  处:《人民长江》2015年第13期90-94,共5页Yangtze River

摘  要:水电站机组经常因主轴密封供水中断的假信号引发保护误动而造成机组的非计划停运,从而影响机组的稳定运行以及电网对电站的考核。以越南某水电站机组主轴密封供水系统为例,对引起主轴密封供水中断的主要因素展开了分析,同时,对两种不同类型流量计的现场实测结果进行了对比。结果表明,电磁流量计误报是引起水电站事故停机的直接原因,而水电站内的电磁干扰及震动等则是引起电磁流量计误报的主要因素。由分析及对比结果可以看出,电磁流量计对使用环境的要求较高,因此,不推荐将其用于环境较为恶劣,特别是主轴密封供水系统对可靠性要求较高的水电站中。Emergency shutdown accidents, due to the fake signals of break - off of water supply of main shaft seal, often occur to the generator units in the hydropower plant, which affect the stable operation of the units as well as the assessment of the hydropower plant by the grid. Taking the main shaft seal water supply system in a hydropower plant in Vietnam for example, the main factors that cause the break - off of the water supply for main shaft seal are analyzed. Through comparing the test results at site measured by two flow meters of different types, it is found that the fake signal sent by the electromagnetic flow meter is the direct cause of the units'emergency shutdown accident and that the electromagnetic interference and vibration inside the plant are the main factors causing the fake signal. The analysis and comparison reveal that the use of electromagnetic flow meter requires a fine environment of the hydropower plant, so it is not suggested to be used in the main shaft seal water supply system of hydropower plants that are in a harsh environment.

关 键 词:主轴密封 供水中断 事故停机 电磁流量计 超声波流量计 越南 

分 类 号:TV734[水利工程—水利水电工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象