变电站端子箱铜包铝电缆屏蔽线的腐蚀现象、机理与防护措施  被引量:3

Corrosion Mechanism and Protection Methods of Copper Clad Aluminum Shielding Cables in Substation Terminal Boxes

在线阅读下载全文

作  者:张洲全[1] 黎小秋[1] 涂湛 何正龙[1] 朱辉[1] 江波[1] 肖文凯[2] 朱黎[2] 

机构地区:[1]国网江西省电力科学研究院,江西南昌330096 [2]武汉大学动力与机械学院,湖北武汉430072

出  处:《材料保护》2015年第9期63-65,9,共3页Materials Protection

摘  要:变电站端子箱中的铜包铝电缆屏蔽线腐蚀严重,通过对其腐蚀产物及横截面的电镜(SEM)扫描、能谱(EDS)和X射线衍射分析,分别用稀HCl,Na Cl和Na OH溶液进行盐雾腐蚀,验证了其腐蚀机理;又分别采用K2Cr2O7,苯丙三氮唑和823溶液进行了防护效果试验。结果表明:腐蚀产物中存在Cl元素,Al Cl3及Cu Cl等物质,阻火泥和屏蔽线外包覆材料中也有大量Cl元素;HCl溶液使铜包铝电缆屏蔽线腐蚀速率最快;823溶液浸泡对铜包铝电缆屏蔽线的防护效果最好。Copper clad aluminum shielding cables in substation terminal boxes often suffer severe corrosion. In this paper,corrosion mechanism of copper clad aluminum shielding cables was investigated based on observation and analysis of the cross section of the corroded wire and corrosion products with scanning electron microscope( SEM),energy dispersive spectrometer( EDS) and X-ray diffraction( XRD) as well as salt spray tests with HCl,NaC l,NaO H solutions respectively. Moreover,the protection efficiencies were tested with K2Cr2O7 solution,BTA solution and 823 solution respectively. Results showed that Cl element existed in the corrosion products,and it was also found in the fireproofing mud and coating materials of the cables. HCl solution corroded the wire the fastest,and the 823 treating fluid could protect the copper in acidic environment the best.

关 键 词:铜包铝电缆线 酸性化学腐蚀 电化学腐蚀 防护措施 

分 类 号:TM63[电气工程—电力系统及自动化] TG172[金属学及工艺—金属表面处理]

 