Enclosure Fire-induced Temperature: Review and Model Modification for Horizontal Vented Space  

Enclosure Fire-induced Temperature: Review and Model Modification for Horizontal Vented Space

在线阅读下载全文

作  者:ZHANG Jiaqing FAN Minghao LI Wei DU Xiaofeng WU Haicheng WANG Shuping 

机构地区:[1]State Grid Anhui Electric Power Research Institute [2]Anhui Province Key Laboratory of Electric Fire and Safety Protection

出  处:《Journal of Thermal Science》2015年第6期562-565,共4页热科学学报(英文版)

基  金:supported by the Anhui Provincial Natural Science Foundation(1408085MKL94)

摘  要:Correlations of fire-induced temperature have been reviewed and revisited.The impact of XY factors,i.e.,the relative locations of the fire source and vent,on temperature models of ceiling-vented compartments could be reflected by the exponents of the two dimensionless terms which represent the ratio of the total energy to energy released through the ceiling vent,and the ratio of the energy lost through the walls to the energy released through the ceiling vent.For fires not located directly below the ceiling vent,the temperature rise was proportional to two thirds of the power of the heat release rate,while for fires immediately beneath this vent,the temperature rise was proportional to four thirds the power of the heat release rate,and was inversely proportional to one sixth the power of the ceiling vent size.

关 键 词:temperature model temperature rise compartment fire ceiling vent 

分 类 号:TU998.1[建筑科学—市政工程] TG333.71[金属学及工艺—金属压力加工]

 