检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]湖北师范学院电与控制工程学院
出 处:《智慧工厂》2015年第10期72-75,共4页Smart Factory
基 金:多变量多通道网络化系统性能极限与优化设计(61100076)
摘 要:为了充分利用矿井高压电网发生单相接地故障时的故障信息,以提高漏电故障选线正确率和准确率,提出了一种基于五次谐波比幅比相的选线判据。该判据以五次谐波固有的特性为出发点,以中性点经消弧线圈接地方式发生母线和线路接地故障为研究对象,在漏电故障正确检测并启动后利用漏电故障后五次谐波的幅值和相位的双重比较后找到最终选线结果。仿真验证了该选线判据的正确性。To fully utilize the fault information of mine the high voltage power grid in the single-phase ground fault, In order to improve the accuracy of fault location accuracy and leakage, Put forward a line selection criterion based on the five harmonic of the comparison of the amplitude and phase. This criterion according to the five harmonic of inherent characteristics as the starting point, With the neutral point of the arc suppression coil grounding of bus and line ground fault as the research object, Find the results of the final route selection in the double comparison of the amplitude and phase of the fifth harmonic after launching the use of leakage fault. The simulation verified the correctness of the line selection criterion.
分 类 号:TM711[电气工程—电力系统及自动化]
正在载入数据...