基于报文优先级的智能变电站母线保护网跳方式研究  

Research of Busbar Protection Network Trip Mode in Smart Substation Based on Message Priority

在线阅读下载全文

作  者:张志鹏[1] 何磊[2] 梁猛[1] 

机构地区:[1]河北省电力勘测设计研究院,石家庄050031 [2]国网河北省电力公司电力科学研究院,石家庄050021

出  处:《河北电力技术》2015年第5期8-11,共4页Hebei Electric Power

摘  要:介绍母线保护直采直跳方式的特点及网跳方式的延时问题,通过母线网跳延时计算实例分析网跳方式的特点,论证了各电压等级母线保护网跳方案的可靠性,提出各电压等级母线保护合理的跳闸方式,以提高跳闸的可靠性、简化网络连接,节省变电站投资。This paper analyses the characteristic of network trip mode in smart substation,calculates the busbar protection tripping delay under the two typical main connections of 220 kV and above voltage level in detailed,demonstrates the measures to reduce the queuing delay of network message,put forwards that the real-time could be significantly improved if the busbar protection trip message was seted to the highest priority,and could avoid the complex measures of message filtering.Demonstrates the reliability of busbar protection network trip scheme under every voltage level.,put forwards the reasonable busbar protection trip modes of every voltage level,to improve the reliability of the trip,simplifies the network connection,reduce the substation investment outlay.

关 键 词:智能变电站 母线保护 跳闸方式 网络延时 优先级 

分 类 号:TM63[电气工程—电力系统及自动化]

 