检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:庞先海[1] 甄利[2] 贾志辉[2] 李晓峰[1]
机构地区:[1]国网河北省电力公司电力科学研究院,石家庄050021 [2]国网河北省电力公司,石家庄050021
出 处:《河北电力技术》2015年第5期46-49,共4页Hebei Electric Power
摘 要:介绍高压隔离开关过热缺陷的判断依据,以及河北省南部电网高压隔离开关的过热缺陷情况,分析缺陷发生的原因,认为其主要原因是老旧隔离开关设计结构不合理、元件质量不良、现场安装工艺不良和运行维护不当,提出隔离开关过热缺陷的反事故措施。According to overheating defects of high-voltage disconnecting switch,the causes for defects have been analyzed,and the main reason is that the design structure not reasonable of old disconnecting switch,the bad component quality,the badly spot install craft and the not appropriate of maintenance.Combined with application in the Hebei south network of disconnecting switch,the analysis of typical defects and the processing methods have been discussed,and the preventive measures have been proposed.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.175