检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]河南理工大学电气工程与自动化学院,焦作454003
出 处:《电子测量技术》2015年第12期6-11,共6页Electronic Measurement Technology
基 金:国家自然科学基金青年基金(61405055);河南省产学研基金资助项目(132107000027)
摘 要:井下高压供电系统中,不能通过在现场做短路实验判断保护定值是否满足选择性与可靠性要求,故本文提出了煤矿井下高压电网保护定值仿真校验系统,通过该系统模拟井下故障检验保护定值的选择性与可靠性。提出了井下高压电网保护定值仿真校验系统整体设计方案,基于广度优先搜索算法对井下供电系统进行拓扑自学习,以获取的拓扑模型为基础提出了故障电流计算方法和定时过流保护、瞬时速断保护、过负荷保护的仿真校验算法。实验结果表明,系统能够检验速断保护与定时过流保护配合是否合理,以及各段保护当前设置是否会造成停电面积扩大等问题,有效实现了井下高压供电系统继电保护定值的仿真检验。In the coal mine high voltage power supply system,the protection setting value whether meets the selectivity and reliability cannot be determined by short circuit experiment in the field,so this paper propose the simulation test system of protection setting value in coal mine underground high voltage network,to simulate the selectivity and reliability of underground flaut detection protection setting value.The whole design scheme of simulation protection setting value in coal mine underground high voltage power network is introduced,breadth-first search algorithm based topology self-learning of coal mine underground supply systems is carried out,based on the obtained topology model,the simulation calibration algorithm of the fault current calculation,timing over-current protection,transient speed circuit protection and overload protection is proposed.The experimental results show that the system can test whether the coordination between timing over-current protection and transient speed circuit protection is reasonable,and whether the current settings of each segmental will cause blackout area expanding,and effectively realize the simulation test of underground high-voltage power system relay protection setting.
关 键 词:继电保护 整定计算 广度优先算法 故障电流 仿真校验
分 类 号:TM77[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.171