一点接地及四极开关  被引量:6

Single- point Earthing and Four-pole Switch

在线阅读下载全文

作  者:凌智敏 

机构地区:[1]悉地国际设计顾问(深圳)有限公司,广东省深圳市518057

出  处:《建筑电气》2016年第2期8-17,共10页Building Electricity

摘  要:一点接地及四极开关均是治理杂散电流、杂散电磁干扰的措施,介绍"一点接地"及"四极开关"治理杂散电流的机理,提出:应优先选用"一点接地";当变配电所与发电机房相距远采用"四极开关"时,应加强维护管理将"断零"的可能降到最低;有条件时可选用高压发电机组与市电进行切换;提示注意"一点接地"与PE线接地的区别。Single-point earthing and four-pole switch are both measures to eliminate stray current and electromagnetic interference. This article introduces the mechanism of " single-point earthing" and "four- pole switch" to control stray current, and puts forward the following ideas: "single-point earthing" is preferred; when "four-pole switch" is adopted due to long distance from substation and distribution station to generator room, maintenance needs to be reinforced to minimize the possibility of "faulted neutral line"; high-voltage generator set, if available, can be adopted to switch with mains supply; attention should be paid to differentiate "single-point earthing" from PE conductor earthing.

关 键 词:杂散电流 杂散电磁干扰:低压配电系统电源侧接地 一点接地 四极开关 多电源系统 双电源切换装置(ATSE装置) 

分 类 号:TU852[建筑科学]

 