榄普一线500kV线路取消架空地线防雷性能分析  

Analysis of Maximum Allowable Lightning Current on Lanpu No.1 Line When Canceling Earth Line

在线阅读下载全文

作  者:龚奕宇[1] 王言[2] 范松海[1] 雷云泽 

机构地区:[1]国网四川电力科学研究院,成都610000 [2]清华大学深圳研究生院,深圳518055

出  处:《环境技术》2016年第1期36-38,52,共4页Environmental Technology

摘  要:榄普一线500 k V线路由于地线覆冰严重,多次出现线路跳闸、地线断裂等事故,因此需要将架空地线取消。结合行波法和ATP-EMTP电磁暂态分析,对取消地线前后榄普一线的耐雷强度进行了仿真计算。计算结果表明,取消地线后雷击基本都变为绕击,并且绕击耐雷强度和反击耐雷强度均有所降低,需要采用其他防雷措施进行保护。Lanpu No.1 overhead transmission line has occurred many line trip and fracture of earth line by the reason of seriously covering ice of earth line. So it' s a necessity to cancel the earth line. By using the traveling wave method and Electromagnetic Transients Program, this paper calculates the maximum a11owable lightning current of Lanpu No. 1 line with and without earth line respectively. The result shows that firstly, when canceling the earth transmission: secon shielding failure or dly, the maximum allowable lightning cu back flashover. So Lanpu No. 1 line needs line, the lightning always strikes the rrent decreases whether it' s lightning other protection measure.

关 键 词:榄普一线 取消地线 耐雷强度 ATP-EMTP 

分 类 号:TM863[电气工程—高电压与绝缘技术]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象