±800kV特高压直流输电线路单极接地故障过电压产生机理及影响因素  被引量:18

Overvoltage generation mechanism during single-pole grounding fault of ±800 kV UHVDC transmission lines and its influencing factors

在线阅读下载全文

作  者:周浩[1] 李济沅 王东举[1] 邱玉婷[1] 李莎[1] 韩雨川 

机构地区:[1]浙江大学电气工程学院,浙江杭州310027

出  处:《电力自动化设备》2016年第4期1-6,13,共7页Electric Power Automation Equipment

基  金:国家重点基础研究发展计划(973计划)资助项目(2011CB209405)~~

摘  要:将特高压直流输电线路单极接地故障过电压分成第一次跃升和第二次跃升2个过程,并基于极线间的电磁耦合作用和波过程阐述了2次电压跃升的产生机理;分析了直流滤波器主电容、直流滤波器型式、直流控制系统、杆塔接地电阻、线路中点杆塔是否装设避雷器、输电线路参数和输送功率等多种因素对该过电压的影响。仿真结果表明,直流滤波器主电容参数是限制单极接地故障过电压的关键因素,其他因素对该过电压影响不大,为控制过电压幅值不超过额定电压的1.7倍,建议±800 k V特高压线路的直流滤波器主电容参数取值范围为1-2μF。The overvoltage process of single-pole grounding fault of UHVDC transmission line is divided into two parts:the first voltage jump and the second voltage jump. The generation mechanism of two voltage jumps is studied based on the electromagnetic coupling between two poles and the wave process. The influences of different factors on the overvoltage are analyzed,such as main DC filter capacitor,DC filter type,DC control system,grounding resistance of line tower,arrester installed on tower at line midpoint,transmission line parameters,transferring power,etc. Simulative results show that,the main capacitor of DC filter is a critical factor to limit the overvoltage while the others have little effect on the overvoltage. Recommended capacitance of the main capacitor of DC filter for ±800 k V UHVDC lines is from 1 μF to 2 μF for limiting the overvoltage within 1.7 times of rated voltage.

关 键 词:特高压输电 直流输电 单极接地故障 过电压 机理分析 故障分析 影响因素 波过程 

分 类 号:TM86[电气工程—高电压与绝缘技术]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象