一起干式空心并联电抗器故障分析及处理  被引量:1

CauseAnalysisandSolutiononDry-typeAirCore ShuntReactorInsulationFault

在线阅读下载全文

作  者:李苏雅[1] 李信喆 董艳唯[1] 马春晓[1] 孟峥峥[1] 刘创华 刘梅[1] 

机构地区:[1]国网天津市电力公司电力科学研究院,天津300384

出  处:《河北电力技术》2016年第3期48-49,56,共3页Hebei Electric Power

摘  要:针对某500kV变电站66kV干式空心并联电抗器发生的贯穿性绝缘故障,进行整体试验和解体分析,认为大量鸟粪附着在电抗器包封间通风道表面、致使表面绝缘降低、以及设备本身设计的绝缘层薄弱是造成该设备绝缘故障的主要原因,提出处理措施,对解决并联电抗器绝缘故障有一定指导意义。Through the integral testing and collapsing analysis,it is pointed that the reducing of surface insulation because of a large number of birds droppings' attaching to the surface of ventilating duct between interlayer and the weakness of insulating layer are the main reasons of 66 kV dry-type air core shunt reactor penetrability insulation fault in 500 kV transformer substation.On this basis,solutions have been proposed,which have a certain significance to solve the penetrability insulation fault of dry-type air core shunt reactor.

关 键 词:并联电抗器 包封 积污 贯穿性绝缘故障 

分 类 号:TM86[电气工程—高电压与绝缘技术]

 