残流增量法在调匝式消弧线圈接地系统中的可行性分析  被引量:2

Feasibility Analysis of Residual Current Increment for Fault line Detecting in Multi-tap Arc-suppression Coil Grounding System

在线阅读下载全文

作  者:姜铁卫 杨锐[1] 夏磊[1] 

机构地区:[1]国电南瑞科技股份有限公司,江苏南京211106

出  处:《江苏电机工程》2016年第4期64-66,共3页Jiangsu Electrical Engineering

摘  要:通过分析调匝式消弧线圈运行中任意两档之间的级差电压变化特征,对采用残流增量法接地故障选线原理的可行性进行分析论证。首先在低压模拟环境中对比理论计算和实际测试数据,验证采用理论方法计算级差电压的可行性,最后以实际工程应用为例,分析其级差电压变化情况,为该方法实际应用提供理论和实践依据。This paper studies the feasibility of residual current increment for fault line detecting by analyzing the differential voltage between two stalls of multi-tap arc-suppression coil. Firstly, the differential voltages in the low voltage simulation model of theoretical calculating and from the practical measuring are compared to verify the feasibility of theoretical arithmetic for differential voltage calculation. Then, taking an actual engineering as an example, the change of differential voltage is analyzed, which provides a theoretical and practical basis for practical application of residual current increment.

关 键 词:残流增量法 调匝式消弧线圈 故障选线 