空冷器螺旋盘管参数对换热和压降影响分析  被引量:1

Analysis of Influence on Heat Exchange and Pressure Drop of Air Cooler Helical-coil Tubes Parameters

在线阅读下载全文

作  者:闫洪远[1,2] 

机构地区:[1]瓦斯灾害监控与应急技术国家重点实验室,重庆400037 [2]中煤科工集团重庆研究院有限公司,重庆400037

出  处:《煤矿机械》2016年第9期37-40,共4页Coal Mine Machinery

基  金:科技部"十二五"科技支撑计划项目(2012BAK04B00)

摘  要:针对矿井降温用螺旋盘管空冷器的结构特点,首次提出了完整的传热和压降计算方法,并对常用的400 k W空冷器进行优化设计。试验测试证明,采用该计算方法设计的换热器的换热性能满足要求,壳侧空气流通阻力和管内水的实测流动阻力分别比计算值平均高出14.4%和6.9%,根据试验测试结果,提出了提高设计精度的方法。In view of the structure characteristics of helical-coil tubes air cooler for mine cooling application, the complete calculation methods of heat transfer and pressure drop is put forward for the first time, and the commonly used 400 kW air cooler is optimized design. Test proved that heat exchange capacity of the heat exchanger designed meet the requirement, the air flow resistance and water of flow resistance is higher than the average calculated value of 14.4% and 6.9% respectively, according to the test results, a method to improve the design accuracy is put forward.

关 键 词:螺旋盘管 空冷器 换热 流通阻力 