贵州信息园数据中心智能新风系统的设计与应用  被引量:14

Design and application of intelligent outdoor air system for data center in Guizhou information park

在线阅读下载全文

作  者:高景[1] 张军甫[1] 潘庆瑶[1] 夏春华[1] 

机构地区:[1]华信咨询设计研究院有限公司

出  处:《暖通空调》2016年第10期27-32,共6页Heating Ventilating & Air Conditioning

摘  要:根据贵阳地区气候和环境条件,在该数据中心中采用智能新风系统,全部或部分使用外界自然冷源取代传统空调系统供冷。详细介绍了智能新风系统的运行模式、新风比控制及节能率。该项目采用智能新风系统后,预计全年节电量2 880 373kW·h,减少CO_2排放量933 241kg。According to the climate and environmental conditions of Guiyang region, the data center uses the intelligent outdoor air system, which utilizes the natural cold source fully or partly to replace traditional air conditioning system for cooling. Presents the operation modes, outdoor air ratio control and energy saving ratio of the intelligent outdoor air system in detail. The results show that the expected annual electricity saving is 2 880 373 kWh and CO2 emissions reduction is 933 241 kg when using the intelligent outdoor air system.

关 键 词:数据中心 智能新风系统 新风过滤系统 新风比控制 节能率 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]

 