机构地区:[1]黑龙江省电力科学研究院,哈尔滨150030 [2]佳达环保工程公司,江苏宜兴214200
出 处:《黑龙江电力》2016年第5期385-388,共4页Heilongjiang Electric Power
摘 要:为了解决声环境功能区区划升级后变电站厂界噪声未达标问题,笔者根据变电站噪声治理前噪声检测数据,分析了户外变电站背景噪声、站内噪声、厂界噪声存在超标问题的原因,提出了采用吸隔声屏障来控制噪声传播途径的降噪方法。实践应用表明:户外变电站加装隔声屏障后,变电站厂界噪声平均降噪量可达到7 d B(A),低于国家标准规定的环境噪声限值。In order to reduce the substation boundary noise to the standard after upgrading the division of the functional regions for sound environment,the author analyzed,according to the detection data before noise control in the substation,the reason for excessive background noise,indoor noise and boundary noise of outdoor substation,and proposed to reduce noise by sound insulation screen which controlled the transmission route of noise. The result shows that,in outdoor substation with sound insulation screen,boundary noise reduces by 7 d B( A),which is lower than the environmental noise limit specified in national standard.
分 类 号:TM63[电气工程—电力系统及自动化]