作 者:张德泉[1] 罗深增 李银红[2] ZHANG Dequan LUO Shenzeng LI Yinhong(Central China Branch of State Grid Corporation of China,Wuhan 430077,China State Key Laboratory of Advanced Electromagnetic Engineering and Technology,School of Electrical and Electronic Engineering, Huazhong University of Science and Technology,Wuhan 430074,China)
机构地区:[1]国家电网公司华中分部,湖北武汉430077 [2]华中科技大学电气与电子工程学院强电磁工程与新技术国家重点实验室,湖北武汉430074
出 处:《电力自动化设备》2016年第11期127-132,共6页Electric Power Automation Equipment
摘 要:针对线路中间带并联电抗器的长距离输电线路提出了基于双端工频量的非同步故障定位算法。对于等值阻抗固定的并联电抗器,采用故障前的双端相量估计并联电抗器的实际等值阻抗,从而基于故障后正序网络得到故障点位置。对于可控并联电抗器或故障前数据无法获取的情况,还提出了一种与并联电抗器模型无关的故障定位算法,根据不同故障类型的故障边界条件,利用故障点电压电流相位特性构造定位函数,分析表明该函数在相应定位区间具有单调变化特性,因而各定位区间不存在伪根,求解快速。所提算法均基于分布参数模型,双端数据不同步角采用故障前或故障后测量相量进行补偿。基于PSCAD/EMTDC和MATLAB的仿真结果表明,所提方法计算简单、精度高,对不同步角、故障类型、过渡电阻、故障位置均有较好的适用性。An asynchronous fault location algorithm based on the power-frequency measurements at two terminals is proposed for long transmission line with shunt reactor in middle. For the shunt reactor with fixed equivalent impedance,its equivalent impedance is estimated with the pre-fault phasors of two terminals and the fault is located based on post-fault positive-sequence network. For the controllable shunt reactor or that without pre-fault data,a fault location algorithm irrelative to the shunt reactor model is proposed,which exploits the characteristics of voltage and current phasors at fault point to construct the fault location function according to the boundary conditions of different fault types. Analysis shows that,the fault location function has monotonicity in the corresponding location sections,which means it can be quickly solved because there is no false root in a location section. The proposed algorithms are both based on the distributed-parameter line model and the asynchronous phasor of two terminal data is compensated by pre-or post-fault measurements. The simulative results based on PSCAD / EMTDC and MATLAB show that,the proposed algorithms are simple,accurate and suitable for different asynchronization angles,fault types,fault locations and transition resistances.
关 键 词:双端非同步相量 故障定位 并联电抗器 分布参数模型 输电线路
分 类 号:TM73[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.14.12.254