宜城板桥风电场入网电能质量测试及谐波治理  被引量:1

Yicheng Banqiao Wind Power Accessing the Power Grid Power Quality Test and Harmonic Control

在线阅读下载全文

作  者:胡斌[1] 舒欣[1] 王易[1] 

机构地区:[1]国网湖北省电力公司电力科学研究院,湖北武汉430077

出  处:《湖北电力》2016年第6期27-32,共6页Hubei Electric Power

摘  要:对湖北华润宜城板桥风电场的基本情况、风电场对电能质量影响的原理、风电场入网的电能质量技术规定进行了阐述,重点分析了板桥风电场入网电能质量检测及谐波治理。针对湖北华润宜城板桥风电场入网检测时发现的公共连接点处4次谐波电流超标问题,经测试分析给出了超标的原因及治理建议;风电场根据建议联系设备厂家,对相关设备进行调整,完成谐波治理;最后经检测电能质量合格,治理成功。The basic situation of Hubei Huayun Yicheng Banqiao wind farm,wind power accessing the power grid power quality technical requirements are described,the implementation of Banqiao wind power access power quality detection and harmonic control are analyzed in detail.Common connection point found in Hubei Huarun Yicheng Banqiao wind power accessing the power grid power testing when the 4 harmonic current exceed the standard,the causes and treatment recommendations are analyzed by tests.According to the proposal,the equipment manufacturers are contacted to adjust the relevant equipments,harmonic is controlled.Finally,the power quality is qualified,and the management is successful.

关 键 词:谐波治理 风力发电 直驱式同步电机 电能质量 

分 类 号:TM727.2[电气工程—电力系统及自动化]

 