检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:潘英吉 周和平 PAN Yingji ZHOU Heping(Jilin Power Supply Company, State Grid, Jilin 132001, China Jilin Electric Power Equipment Installation Co. , Ltd. , Jilin 132011, China)
机构地区:[1]国网吉林供电公司,吉林吉林132001 [2]吉林市电力设备安装有限公司,吉林吉林132011
出 处:《现代建筑电气》2016年第11期29-31,共3页Modern Architecture Electric
摘 要:分析了10kV架空线路的雷害事故,探讨了避雷器有效保护范围,并对避雷器进行周期预防性试验。提出要结合国家电力行业标准DL/T1292—2013《配电网架空绝缘线路雷击断线防护导则》,沿线杆塔均应逐级逐相安装避雷器,且应尽量降低避雷器上的残压,消除保护盲区,确保10kV架空线路的安全运行。This paper analyzed the lightning accidents of 10 kV overhead line, and discussed the effective operation range of surge arrester. The preventive test of surge arrester was carried out. It is pointed out that combined by the national electric power industry standard DL/T 1292-2013 ,the surge arrester should be installed along the line tower, and the residual voltage on surge arrester should be reduced,which eliminates the blind spot protection and insures the safe operation of 10 kV overhead line.
关 键 词:10 KV线路 雷害事故分析 防护措施 预防性试验
分 类 号:TM863[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.117