检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]中国南方电网超高压输电公司广州局,广州510663 [2]山东科汇电力自动化股份有限公司,山东淄博255087
出 处:《山东电力技术》2016年第12期15-19,共5页Shandong Electric Power
摘 要:分析架空线—海底电缆混合线路发生故障后行波的传播特点,并在此基础上提出一种利用暂态行波的架空线—海底电缆混合线路故障定位方法,以架空线与海底电缆连接点处发生故障后暂态行波传播到混合线路两端母线的时间差值为整定值序列,当架空线—海底电缆混合线路发生故障后,通过所测得的故障暂态行波传播到混合线路两端母线的时间差值与整定值序列进行比较确定故障区段,再通过相应测距公式进行测距计算。PSCAD仿真结果表明,本方法可以准确可靠地测出故障点。Traveling wave propagation characteristics of the overhead line-submarine cable are analyzed after faults, and a fault location method based on transient travelling wave is proposed. The time difference of the transient traveling waves arrived buses of the overhead line and the submarine cable after the fault occurred at the connection point of the overhead line and the submarine cable is set to the setting value sequence. The preliminary fault location is given after comparing the time different with the setting value sequence. Then the fault location is decided using corresponding distance formula. PSCAD simulation shows the proposed method is feasible and the accuracy of fault location is improved obviously.
分 类 号:TM721[电气工程—电力系统及自动化]