检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]国网山西省电力公司电力科学研究院,山西太原030001 [2]昆明理工大学,云南昆明650504
出 处:《山西电力》2017年第1期6-9,共4页Shanxi Electric Power
摘 要:近几年,智能变电站在运行过程中,发生多起由于合并单元相关问题导致的保护误动事件,对电网的运行造成一定影响。基于研究现阶段智能变电站的保护配置,深入分析了多起智能变电站的保护误动事件。研究表明:多起事件的发生是由于智能变电站部分合并单元工艺质量和逻辑设计存在问题,现场调试、检修和运维人员对于智能变电站二次系统的调试启动、检修机制和运维安措等方面技术掌握不到位导致的。针对此,提出了相应的整改意见。Faults of relay protection malfunction occurred several times during the operation process of smart substations recently, which has great influences on power grid. Based on the research of protection configuration of smart substation, the paper, analyzed several events of relay protection malfunction in smart substations. Investigations show that the accidents were imputed to poor quality of merge units and defect of logic design. In addition, commissioning and maintenance staffs deserve the blame for the faults due to their skills not coming up to standard. In view of the problems, corresponding suggestions were put forward ultimately.