摘 要:介绍了光纤测温技术和CFD气流模拟软件结合,可得到机房能耗的分布情况。结合互联网数据中心(IDC)机房实例,分析了在IDC机房中应用光纤测温技术的社会效益和经济效益。结果表明,光纤测温技术具有较高的温度精度和定位精度,能监测机房及机柜环境温度和能耗情况;利用CFD 6SigmaRoom软件可较精确模拟机房及机柜的温度气流场分布,实现空调系统的精准调控,达到节能降耗的目的。This paper introduced the combination of the optical fiber temperature measurement technology and computational fluid dynamics (CFD) simulation software in Internet data center(IDC) room,which obtained the energy consumption distribution. Combining by an IDC room as an example ,the social benefits and economic benefits using the application of optical fiber temperature measurement technology were analyzed in IDC room. The results show that the optical fiber temperature measurement technology has the higher temperature accuracy and positioning accuracy, and can monitor the environment temperature and energy consumption in IDC room or cabinet. The CFD 6SigmaRoom simulation software accurately simulates the temperature flow field distribution, and realized the accurate positioning of air conditioning system,to achieve the saving energy and reducing consumption.