利用竖井实现多层建筑复合通风的盐水实验研究  被引量:1

Salt-water simulation experiment research of stack-based hybrid ventilation for multi-story buildings

在线阅读下载全文

作  者:阳东[1] 丁瑶[1] 李萍[1] 

机构地区:[1]重庆大学

出  处:《暖通空调》2017年第4期104-108,95,共6页Heating Ventilating & Air Conditioning

基  金:国家自然科学基金资助项目(编号:51578087)

摘  要:通过盐水实验,考查利用竖井实现多层建筑复合通风的可行性。介绍了基于竖井的多层建筑复合通风方案及其定量设计方法。阐述了盐水实验原理、相似率及参数选择方法,研究了建筑复合通风盐水实验的相似准则。以一个缩尺寸(1∶40)的3层建筑为研究对象,进行了3种工况盐水实验。结果表明,对于多层建筑,竖井式复合通风是一种切实可行的通风方案。Examines the feasibility of the stack-based hybrid ventilation theory by means of the salt- water model experiment. Presents a stack-based hybrid ventilation scheme for multi-story buildings and the quantitative design method. Expounds the principle of the salt-water experiment, similarity rate and the methods of parameter selection, and studies the similarity criterion of salt-water experiment. Taking a scale-down (1 : 40) three-layer building as the experimental object, carries out the salt-water experiments under three different conditions. The results show that the stack-based hybrid ventilation is a kind of feasible scheme for multistory buildings.

关 键 词:竖井 复合通风 多层建筑 盐水实验 相似准则 热压 

分 类 号:TU834.3[建筑科学—供热、供燃气、通风及空调工程]

 