作 者:吕智
机构地区:[1]广东浩特普尔空调有限公司,广东佛山528222
出 处:《企业技术开发》2017年第4期41-43,共3页Technological Development of Enterprise
摘 要:文章分析了某高铁站项目的空调系统设计实践,该项目采用基于溶液调湿技术的温湿度独立调节+地源热泵空调系统,冷冻水温度提高至14℃~19℃,显著减少打井数量,比节能规范要求的运行能耗水平再节能35%。文章通过对该项目温湿度独立调节+地源热泵空调系统的介绍,详细阐述了在高铁站应用的特点和具体布置形式,希望对广大一线设计师和从事绿色、节能建筑的工程技术人员有所裨益。This paper analyzes the practice of air conditioning system design of a high speed railway station project.This project adopted the temperature and humidity independent regulation I ground source heat pump air conditioning system based on the solution humidity control technology Due to the chilled water temperature increasingto 14/19O ,the well number decreased greatly.The THIC air-conditioning system made the building energy-saving up to 3 5 % comparing to the conventional air conditioning system that meet Design standard for energy efficiency.This paper presented the detail information of THIC+GSHP air-conditioning system and the characteristics of application and concrete form in high-speed rail station.It was hoped that this paper is helpful for designers and technician who are engaged in energy-saving and green building application.