作 者:刘纯[1] 唐远富[1] 欧阳克俭[1] 刘云龙[1]
机构地区:[1]国网湖南省电力公司电力科学研究院,湖南长沙410007
出 处:《湖南电力》2017年第2期46-50,63,共6页Hunan Electric Power
摘 要:预绞式悬垂线夹因在结构、性能和节能等方面的显著特点被广泛应用。针对某±800 k V输电线路地线预绞式悬垂线夹断裂问题,开展材质检测、机械强度试验和力学计算,检测发现线夹单侧悬垂角为10°,不符合DL/T 763—2013要求。张力试验表明40°出线角时线夹极限张力约为38 k N;且当线夹悬垂角一定时,出线角越大,线夹悬垂套壳承受极限张力越小。脱冰跳跃动力计算发现当前档80%及以上地线脱冰时,后侧线夹出线角增大,对应的地线张力达到线夹的极限荷载。指出线夹由于悬垂角偏小,地线脱冰跳跃致使其断裂。提出对重冰区预绞式悬垂线夹套壳底部变形检查建议。The helical suspension clamp is widely used in terms of structure performance, energy conservation. The failure helical suspension clamp in a ±800 kV transmission line was investigated by means of material property testing, mechanical strength test and mechanical calculation. It was found that the suspension angle of the clamp is 10 degrees, which do not conform to the requirements of the DL/T 763-2013. The tension tests indicated that the ultimate strength of the clamp is about 38kN while the outlet angle is 40 degrees. When the clamp's suspension angle is a constant value, the greater the outlet angle of clamp, the smaller its ultimate strength. The dynamic response of ice shedding-caused vibration was analyzed by finite element method (FEM). The results showed that when ice shedding occurs on 80% and above length of the front span groundwire, the outlet angle of back clamp will increase, and the corresponding tension of ground wire would reach the ultimate strength of clamp. It was pointed out that clamp's fracture is the result of the ice shedding and its small suspension angle. It was suggested that the deformation inspection of helical suspension clamp should be carried out in heavy icing area.
关 键 词:特高压 直流输电线路 预绞丝悬垂线夹 断裂分析 脱冰跳跃 悬垂角
分 类 号:TM752[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.28