检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]国电南京自动化股份有限公司,江苏南京210032 [2]南京国电南自电网自动化有限公司,江苏南京211153
出 处:《四川电力技术》2017年第2期66-70,共5页Sichuan Electric Power Technology
摘 要:讨论了智能变电站中层次化继电保护系统的配置方式,就目前就地保护配置复杂、保护整定繁复、后备保护逐级配合时间长、站域保护工程应用不便等多方面的问题,提出了就地保护的部分后备保护功能向站域保护、区域保护迁移的配置策略;并基于一次设备建模、变电站信息交互来实现就地保护定值自动整定、与就地保护协同的站域后备保护的思路和实例,降低现有继电保护信息流的横向耦合,简化就地保护配置,提升站域后备保护性能。The relay protection configuration in smart substation is discussed. According to the complicated function configura- tion, uncomfortably setting, long operation time of step - by - step backup protection and inconvenient engineering application of station - domain protection, it is proposed that the part of backup protection function is transferred to the station - domain protection or area protection. And based on primary equipment modeling and device information interaction, the ideas and examples are realized that is local protection setting sets by itself automatically and station - domain backup relay protection is cooperated with local protection to optimize local protection. It can reduce the transverse coupling in the existing relay protec- tion, simplify the local protection configuration and improve the performances of station - domain backup protection.
关 键 词:智能变电站 层次化继电保护 一次设备建模 自动整定 协同
分 类 号:TM771[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.185