检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:翟军[1,2] 沈莉[1,2] 李海波[1,2] 周国仲[1,2]
机构地区:[1]中国科学院高能物理研究所,北京100049 [2]东莞中子科学中心,广东东莞523803
出 处:《强激光与粒子束》2017年第7期109-113,共5页High Power Laser and Particle Beams
基 金:基金项目:中国散裂中子源工程
摘 要:对脉冲电源系统72h老练实验过程中高压电缆座打火并被击穿情况进行分析,建立高压电缆终端电场分布等效电路,推导出从电缆终端到金属屏蔽层的电势差公式,从理论上分析高压座被击穿的原因是电缆终端绝缘层未做倒角,空间电荷在此处集聚、温度升高导致的。通过定位被击穿高压座击穿孔的位置验证理论分析的正确性,最后提出高压电缆端部绝缘层处理方法,并做72h老练实验验证了其正确性。By observing and analyzing the sparking and breaking down of the high-voltage cable socket of the pulsed power supply during the 72 hours conditioning experiment, the electrical field distribution equivalent circuit of the terminal of the highvoltage cable was built, the formula of the potential difference from the cable-terminal to the metal shielding layer was conducted. The reason of breakdown is analyzed theoretically in this paper. It is suggested that the un-chamfered insulation of the cable-terminal causes space charge focusing, which then results in a temperature increase leading to the high-voltage cable socket breakdown. The theoretical analysis is proved by the position of the breakdown hole of the high-voltage cable socket. The handling method of insulation of the cable terminal is presented, which was validated by continuous conditioning experiment for 72 hours.
关 键 词:脉冲电源 高压电缆座 电场分布等效电路 电缆终端绝缘层 老练实验
分 类 号:TL507[核科学技术—核技术及应用]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.15