机构地区:[1]电网智能化调度与控制教育部重点实验室(山东大学),山东省济南市250061 [2]国网山东省电力公司济南供电公司,山东省济南市250001
出 处:《电力系统自动化》2017年第12期93-99,共7页Automation of Electric Power Systems
基 金:国家高技术研究发展计划(863计划)资助项目(2012AA050213);山东省重点研发计划资助项目(2015GGX101011)~~
摘 要:逆变型分布式电源区别于传统电源的故障特性导致传统电流保护难以快速可靠切除故障,也影响了现有输电网保护原理直接应用于配电网的动作性能。借鉴电流差动保护原理思想,定义了正序差动阻抗,理论分析了其在区内外故障时的幅值差异,提出了一种适用于有源配电网的正序阻抗差动保护原理。为进一步改善保护性能,有效应对分支负荷的影响,构造了带制动特性的动作判据。针对区内三相金属性短路故障时保护存在的死区问题,利用故障时正序阻抗与正序电流幅值特征构造了辅助判据。与传统电流差动保护相比,所述方法无需两端数据同步采样,对通信要求较低。仿真结果验证了保护原理的有效性。The fault characteristics of the inverter-based distributed generator(IBDG)differ from those of traditional resources,which makes it difficult for traditional current relay to clear fault fast and reliably.Also affected is the action performance of the existing transmission line protection principle directly used in distribution network with IBDG.By drawing on current differential protection for reference,the amplitudes of the defined positive sequence differential impedance for the internal and external fault are analyzed,and a novel positive sequence differential impedance protection principle is proposed to account for the impedance amplitude difference.To further improve the performance,an operation criterion with braking characteristic is constructed to overcome the adverse effects of load branch.An auxiliary criterion based on the amplitude of positive sequence impedance and current is formulated for internal three-phase short circuit faults without transition resistance.Compared with the traditional current differential protection,the proposed protection strategy has no need for synchronized measurement.The feasibility of protection scheme is verified by simulation results.
关 键 词:正序阻抗 差动保护 制动特性 逆变型分布式电源 配电网
分 类 号:TM773[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.145.82.96