一起距离保护误动事例分析以及解决方案  被引量:6

Analysis and Solution of a Distance Protection Mal-operation Case

在线阅读下载全文

作  者:沈军[1] 张洪喜[1] 王忠[1] 赵青春[1] 张春合[1] 朱晓彤[1] 

机构地区:[1]南京南瑞继保电气有限公司,江苏南京211102

出  处:《电力工程技术》2017年第3期100-104,共5页Electric Power Engineering Technology

摘  要:作为后备保护,距离保护广泛用于各电压等级的线路及元件保护,为确保方向性,距离保护一般采用正序电压作为极化电压,但正序极化电压在系统非全相运行工况下可能无法正确反映故障前电压。本文介绍了一起单侧电源系统距离保护Ⅰ段在反向故障时误动的事例,分析了利用正序电压作为距离保护极化电压存在的不足,并提出了相应的解决方案,最终RTDS实验结果验证了本方案的正确性。As a backup protection, distance protection is widely used as line and component protection for each voltage level. In order to ensure the direction, positive sequence voltage is used as the polarization voltage for distance protection.However, the positive sequence polarization voltage may not reflect the pre-fault voltage correetly when the system is in open-phase operating conditions. This paper introduced a mal-operation case of distance protection for a reverse fault,analyzed the disadvantages of using positive sequence polarization voltage, and proposed corresponding solutions. Finally,experiment results of RTDS validate the correctness of the scheme.

关 键 词:距离保护 误动 正序电压 极化电压 工作电压 非全相 

分 类 号:TM73[电气工程—电力系统及自动化]

 