通信基站用热管换热器试验研究和节能分析  被引量:3

Experimental study and energy saving analysis of heat pipe exchangers used in communication base stations

在线阅读下载全文

作  者:郝长生[1] 尤占平[1] Hoo Chongsheng You Zhonping

机构地区:[1]石家庄铁道大学

出  处:《暖通空调》2017年第7期75-79,70,共6页Heating Ventilating & Air Conditioning

基  金:河北省住房和城乡建设厅资助项目(编号:2011-104);河北省自然基金项目(编号:E2014210020)

摘  要:在模拟通信基站内试验研究了分离式热管换热器的性能,得到了热管换热器排热量和排热能效比随室内外温差及风机功率的变化特性。在DeST平台上建立了通信基站的典型模型,计算了空调单独排热工况和热管换热器-空调联合排热工况的运行参数,分析了联合运行工况的节能率、节电量和静态回收期,结果表明,通信基站采用热管换热器具有较大的节能潜力。Experimentally studies the performance of a separated heat pipe in a simulated communication base station, and obtains the changing characters of heat discharge capacity and energy efficiency ratio along with the difference between indoor and outdoor temperatures and the fan power. Builds a typical model of communication base station on DeST platform. Calculates the operation parameters of the air conditioning system in the working conditions of individual heat discharge and combined with the separated heat pipe, respectively. Analyses the energy saving rate, electricity saving rate and static payback period of the combined operating conditions, which proving the strong energy saving ootential of the seoarated heat oioe exchangers used in communication base stations.

关 键 词:分离式热管换热器 通信基站 排热量 排热能效比 模型 试验研究 