40.5kV高压开关柜绝缘故障原因分析及处理  被引量:15

Causes Analysis on 40.5kV High-voltage Switchgear Panel Insulation Fault and Measures

在线阅读下载全文

作  者:庞先海[1] 冀立鹏[2] 景皓[1] 冯建萍 李晓峰[1] Pang Xianhai Ji Lipeng Jing Hao Feng Jianping Li Xiaofeng(State Grid Hebei Electric Power Research Institute, Shijiazhuang 050021, China State Grid Hebei Electric Power Corporation Xingtai Power Supply Branch,Xingtai 054001 ,China Shijiazhuang Sikai Electric Power Construction Co., Ltd. Power Supply Branch,Shijiazhuang 050000 ,China)

机构地区:[1]国网河北省电力公司电力科学研究院,石家庄050021 [2]国网河北省电力公司邢台供电分公司,河北邢台054001 [3]石家庄思凯电力建设有限公司供用电分公司,石家庄050000

出  处:《河北电力技术》2017年第3期31-33,共3页Hebei Electric Power

摘  要:对40.5kV高压开关柜绝缘故障进行统计分析,认为故障率高的主要原因是空气绝缘净距不足、绝缘材料老化、复合绝缘配合不当和绝缘材料质量较差等绝缘缺陷,并对这些绝缘缺陷进行深入分析,分别提出现场已运行和新装用40.5kV高压开关柜的处理措施。The causes for the high of 40.5kV high-voltage switchgear panel insulation fault rate is analyzed,and the main reasons are that the lack of air insulating distance,the aging of insulating material,the improper composite insulation co-ordination,the poor quality of insulating material and so on.This insulation fault is discussed,and the specific preventive measures of the new equipment and operating equipment for 40.5kV high-voltage switchgear panel is proposed.

关 键 词:高压开关柜 绝缘故障 空气绝缘净距 绝缘材料老化 

分 类 号:TM564[电气工程—电器]

 