作 者:张子衿 丛伟[1] 肖静 冯迎春 王安宁 王孟夏[1]
机构地区:[1]山东大学电网智能化调度与控制教育部重点实验室,山东济南250061 [2]国网山东省电力公司检修公司,山东济南250118 [3]国网山东省电力公司调控中心,山东济南250001
出 处:《电力自动化设备》2017年第9期159-165,共7页Electric Power Automation Equipment
基 金:国家自然科学基金资助项目(51377100)~~
摘 要:分析了同杆双回线内部发生接地故障时故障线路及相邻线路上零序反时限过流保护的动作特性。分析结果表明当故障位置与两侧系统参数满足特定条件时,双回线相邻线路上的零序反时限保护可能误动,故障线路两端保护的灵敏度配合可能存在问题。提出一种改变相邻线路保护时间整定系数的方法来避免可能出现的保护误动,该方法通过增加相邻线路保护动作延时来保证双回线保护优先动作,但也给相邻线路保护的速动性带来不利影响。此外故障线路两端保护的动作时间可能相差较大,不利于故障的快速切除。为此设计了基于零序电流变化和零序功率方向的加速方案,无论双回线故障还是双回线相邻线路故障,均能确保故障线路保护优先动作,从而保证各处保护的选择性和速动性。算例仿真验证了分析结论的正确性和所提加速方案的可行性。The operating characteristics of zero-sequence inverse-time overcurrent protections of the faulty and adjacent lines during the internal grounding fault of double-circuit lines on same tower are analyzed and results show that,when the fault location and the system parameters of both sides meet some conditions,the zero-sequence inverse-time overcurrent protections of the adjacent lines may malfunction and the protection sensitivities of two ends of the faulty line may mismatch. It is proposed to change the protection TDS(Time Dial Setting) of adjacent line to avoid the possible malfunction,which ensures the protections of doublecircuit lines function first by increasing the time-delay of the protections of adjacent lines,but also reduces their sensitivity. Besides,the protections at both sides of faulty line may have quite different operating times,unfavourable for the rapid fault removal. Therefore,acceleration schemes respectively based on zero-sequence power direction and zero-sequence current variation are put forward,which ensures the protections of faulty line function first,either double-circuit lines or adjacent lines. The selectivity and sensitivity of all the protections are ensured. Simulative results prove the validity of the analytical results and the feasibility of the proposed acceleration scheme.
关 键 词:继电保护 同杆双回线 零序反时限 过电流保护 加速方案 输电
分 类 号:TM773[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.249