钢塔对间冷散热器换热性能的影响  被引量:6

Influence of steel tower on the heat transfer characteristics of indirect air cooled radiator

在线阅读下载全文

作  者:石磊[1,2] 王锦 薛海君[2] 石诚 

机构地区:[1]北京交通大学土木建筑工程学院,北京100044 [2]双良节能系统股份有限公司,江苏江阴214444 [3]中国国际工程咨询公司,北京100048

出  处:《北京交通大学学报》2017年第4期70-76,共7页JOURNAL OF BEIJING JIAOTONG UNIVERSITY

基  金:中央高校基本科研业务费专项资金(2011JBM266)~~

摘  要:利用计算传热学软件Fluent,在自然通风状态下,对国内首个2×660 MW机组钢结构外覆铝板冷却塔间接空冷散热器的流动和换热性能进行数值模拟、分析和研究.考核工况下,水平加强环对散热器换热量和钢塔通风量的影响约占设计值的2.7%;铝板换热量约占机组排热量的0.6%;随着环境风速的增大,钢塔抽力逐渐降低;当环境风速高于10m/s时,出现塔内热空气流出冷却柱的现象;当环境风速高于20m/s时,塔内出现"穿堂风",间冷散热器的换热量和钢塔通风量明显增加;当环境风速低于12m/s时,随着环境风速的增大,间冷散热器的换热量和钢塔通风量逐渐降低;当环境风速高于12m/s时,随着环境风速增加,间冷换热量和钢塔通风量呈增大趋势.By using the numerical heat transfer software FLUENT,the flow and thermal characteristics of the first 2×660 MW units indirect air cooled radiator(IACR)in China is numerically simulated,analyzed and studied under natural draft,whose steel-structured air cooling tower is coated with aluminum sheet.Under the performance assessment working condition set in this paper,the difference value of the heat transfer amount of IACR and ventilation volume of steel tower between units with and without horizontal stiffening rings takes up about 2.7% of the designed heat transfer amount.The heat transfer amount of aluminum plates takes up about 0.6% of the power units′heat rejection amount.The driving force of steel tower decreases as wind speed increases.Hot air in steel tower flow out through cooling column as wind speed is greater than10m/s.Wind gust through the tower appears as wind speed is greater than 20m/s,and the heat transfer amount of IACR and ventilation volume of steel tower apparently increase.When envi-ronmental wind speed is less than 12m/s,heat transfer amount of IACR and air flow rate of steel tower gradually decrease as wind speed increases.When environmental wind speed is greater than12m/s,heat transfer amount of IACR and air flow rate of steel tower tend to increase as wind speed decreases.When environmental wind speed is greater than 12m/s,heat exchange rate of IACR and air flow rate of steel tower show the tendency of increase as wind speed decreases.

关 键 词:钢塔 间接空冷散热器 数值模拟 空冷塔 自然通风 优化设计 

分 类 号:TK264.1[动力工程及工程热物理—动力机械及工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象