摘  要:针对某±500 kV换流站出现的电压异常波动现象,通过对站内直流电压互感器结构及设计原理进行分析,并搭建了直流电压测量系统进行测试,发现直流电压互感器远端模块存在接地不良的设计缺陷是引起系统测量电压异常的主要原因。针对存在的问题提出了改进措施并加以实施,有效地解决了直流电压互感器电压异常问题,也为今后同类设备的设计及选型提供了一定的参考。In view of the abnormal voltage fluctuation occurred in a certain +500 kV converter station, it is found that the abnormal measurement voltage at the remote module of DC voltage transformer is due to defect design in earthing by way of analysis of both structure and design principle of the DC voltage transformer in the station and of test through setting up DC voltage measurement system. The modification measures for the problem is proposed and implemented, which solves effectively the abnormal voltage issue of DC voltage transformer and also provides a definite reference for the design and selection of similar type of product in the future.

关 键 词:直流电压互感器 电压异常 直流系统 

分 类 号:TM451[电气工程—电器]

 