检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:于竞哲 苏宜靖 周浩[1] 胡列翔[2] 黄晓明 许烽
机构地区:[1]浙江大学电气工程学院,杭州310027 [2]国网浙江省电力公司,杭州310007 [3]国网浙江省电力公司湖州供电公司,湖州313000 [4]国网浙江省电力公司电力科学研究院,杭州310014
出 处:《高电压技术》2017年第11期3653-3660,共8页High Voltage Engineering
基 金:国网浙江省电力公司科技项目(5211DS15002W)~~
摘 要:将交流电缆配电线路改造为直流运行后,准确设计电缆的运行参数能在最大程度上利用原有线路的供电能力。为此,以10 kV电压等级交流配电网中广泛使用的典型3芯交联聚乙烯(XLPE)绝缘电缆为例,根据所选电缆的结构和材料参数,使用有限元分析软件ANSYS建立了电缆温度场和电场耦合仿真模型,并在直流运行方式为双极式的条件下对电缆的温度场和电场进行了仿真。研究结果表明:对于所选典型电缆,为避免空间电荷效应的影响,其直流电压等级的取值范围为±10~±20 kV;当电缆在温度为40℃的空气环境中敷设而且导体的长期工作温度为70℃时,其载流量约为440 A;同时,其最大输送功率约为改造前的1.3~2.6倍。所得结论以及所用设计条件、步骤可为相关工程提供一定参考。After the AC cable distribution line is transformed into DC operation, the use of the original line's power sup- ply capacity can be maximized by designing the operation parameters of the cable accurately. We established a simulation model for the temperature and the electric field coupling according to the parameters of the typical three-core XLPE cable widely used in 10 kV AC distribution network by using the finite element analysis software ANSYS. The temperature field and the transient and steady state electric field were simulated and analyzed for the cable in DC bipolar operation. The results show that, for the selected typical cable, when it lays in the 40 ~C air and the long-term working temperature of the conductor is 70 ~C, the current carrying capacity of the cables is about 440 A. Meanwhile, in order to avoid the ef- fect of the space charge, the DC voltage range of the selected cable is ~ 10--~x20 kV, and its maximum transmission power is 1.3-2.6 times before reconstruction. The conclusions as well as the design conditions and procedures can provide some references for the related engineering.
关 键 词:10 KV XLPE电缆 交改直 载流量 直流电压等级 ANSYS仿真
分 类 号:TM75[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.200