检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]广西电网有限责任公司电力科学研究院,广西南宁530023
出 处:《广西电力》2017年第6期34-37,共4页Guangxi Electric Power
摘 要:广西某110 kV城区变压站围墙外1 m噪声超标严重,附近居民投诉较多。为解决该变电站噪声超标问题,利用变压器噪声衰减计算软件分析各种噪声治理措施的合理性和经济性。根据计算结果进行分析,得出在变压器西侧约3 m处增设厚200 mm、高5 m的微孔纤维复合吸声板吸声墙是最有效的治理措施。该措施实施后,围墙外1m及噪声敏感点的噪声值均符合标准要求。The 1 meter noise outside the wall of an 110 kV urban substation seriously exceeds the standard in Guangxi, which caused more complaints from nearby residents. In order to the noise exceeding the standard problem of the substation, reasonability and economy of all noise control measures are analyzed by the transformer noise attenuation calculation software. By the analysis based on calculation results, it is obtained that the most effective control measures is the addition of a 200 mm thick and 5 meter tall micro fiber composite sound absorption board wall at about 3 meters of transformer west side. After the implementation of the measure, all the noise values at 1 meter outside the wall and sensitive points meet the standard requirements.
分 类 号:TM63[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.147