直燃型溴化锂吸收式冷热水机组夏季运行工况能耗分析与节能优化  被引量:2

Energy consumption analysis and energy saving optimization of direct-fired lithium-bromide absorption-type water chiller in summer operation condition

在线阅读下载全文

作  者:孟强 陈聪 武文洁 熊亚选[2] 

机构地区:[1]北京长峰机械动力有限责任公司,北京市通州区101100 [2]北京建筑大学

出  处:《暖通空调》2018年第3期69-74,共6页Heating Ventilating & Air Conditioning

摘  要:测试了某机房冷热水机组在未运行机组冷水进出口阀门关闭与开启2种不同运行状态下的COP和制冷量,结果表明,阀门关闭时的COP要高于阀门开启时。分析了冷水泵、冷却水泵和冷却塔运行中存在的问题,提出了改进措施。Tests the COP and cooling capacity of a chilled and hot water unit in a machine room under two different operating conditions of the closed and open inlet and outlet valves of chilled water. The results show that the COP at the condition of closed valve is higher than that at the open valve. Analyses the operating problems of chilled water pump, cooling water pump and cooling tower, and puts forward the improvement measures.

关 键 词:吸收式冷热水机组 变频调速 节能优化 冷水泵 冷却水泵 冷却塔 

分 类 号:TU831.4[建筑科学—供热、供燃气、通风及空调工程]

 