过冷却回路对多联机性能的影响  

Effect of Subcooling Circuit on Performance of Multi-split VRF System

在线阅读下载全文

作  者:李子爱[1] 张国辉 王宝龙[1] 李先庭[1] 石文星[1] Li Zi′ai;Zhang Guohui;Wang Baolong;Li Xianting;Shi Wenxing(Department of Building Science,Tsinghua University,Beijing,100084,China)

机构地区:[1]清华大学建筑技术科学系,北京100084

出  处:《制冷学报》2018年第5期36-46,共11页Journal of Refrigeration

基  金:国家重点研发计划项目(2016YFC0700304)资助~~

摘  要:本文实验研究了过冷却回路对多联机制冷和制热性能的影响,并提出多联机过冷却回路的控制策略。结果表明:室内、外机之间的配管越长、负荷率越大及室外机入口水温越高,过冷却回路对多联机制冷量和EER的优化潜力越大;过冷却回路对制热量和制热COP均无显著影响。提出将室外机模块出口过冷度、压缩机排气温度和过冷却换热器节流侧出口过热度作为过冷却回路的开启判据和控制目标参数。The effect of the subcooling circuit on the cooling and heating performances of a multi-split VRF system and a control strategyfor multi-split VRF system with subcooling circuit is proposed in the paper. The results show that the subcooling circuit has a greater po?tential for improving the cooling capacity and the EER of the multi?split VRF system when the VRF system has a longer pipeline betweenthe indoor units and the outdoor, a larger part?load ratio and a higher inlet water temperature of the outdoor unit, while the subcooling circuit has less influence on heating capacity and the COP of the multi-split VRF system. Based on the results, a control strategy of the subcooling circuit is proposed, which takes the outlet subcooling degree of the outdoor unit, the compressor discharge temperature and the outlet superheat degree of the bypass stream in the subcooling heat exchanger as decision parameters and control targets of the subcooling circuit.

关 键 词:多联机 过冷却回路 控制策略 配管长度 

分 类 号:TB611[一般工业技术—制冷工程] TQ051.5[化学工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象