分接开关受潮导致变压器绝缘电阻降低的分析  被引量:2

Analysis on the insulation resistance reduction of transformer due to tap switch moisture

在线阅读下载全文

作  者:欧阳进[1] 胡海宁[1] 蒯强[1] 周劲武 易登辉 OUYANG Jin;HU Haining;KUAI Qiang;ZHOU Jinwu;Yi Denghui(Changsha Power Supply Company of State Grid Hunan Power Company,Changsha Hunan 410000,China)

机构地区:[1]国网湖南省电力公司长沙供电公司,湖南长沙410000

出  处:《宁夏电力》2018年第4期50-52,65,共4页Ningxia Electric Power

摘  要:针对三绕组有载调压开关变压器绝缘电阻不合格问题展开检查,分析了变压器高压侧接线及绝缘电阻测试原理,综合分析各项试验,初步判断绝缘下降原因在分接开关。通过分接开关试验,发现有载分接开关进水受潮,造成绝缘电阻降低,经过处理绝缘电阻恢复合格。For the unqualified transformer insulation resistance of the three winding on - load tap changer, the high voltage side connection and the testing principle of transformer insulation resistance are analyzed. Through comprehensivly analyzing each test, the cause of the insulation switch, it is preliminarily concluded to be tap is found that on - load tap changer changing switch. By the test of tap changing dampened by the inlet water, and lead to the insulation resistance reduction. So through the treatment method the insulation resistance is qualified.

关 键 词:有载调压开关 变压器 绝缘电阻 受潮 

分 类 号:TM835.4[电气工程—高电压与绝缘技术]

 