广西玉林供电局配电网系统PT谐振过电压研究  被引量:5

Study on Resonance Overvoltage Due to Saturated PT in Distr- ibution System of Yulin Power Supply Company in Guangxi

在线阅读下载全文

作  者:谢伟山[1] 鲁铁成[2] 孙结中[1] 易智飞[1] 陈益伟 

机构地区:[1]广西电力试验研究院,广西南宁530023 [2]武汉大学电气工程学院 [3]广西玉林供电局,广西玉林537000

出  处:《广西电力》2002年第3期24-29,26,共7页Guangxi Electric Power

摘  要:通过高压原形模拟试验和仿真计算 ,得出配电系统引起PT铁磁谐振的参数配合范围。这一范围的确定 ,对验算使用同类PT的各变电站配电系统是否发生PT谐振过电压 ,如何避开谐振区域 ,提供了科学依据。文中还将试验结论运用于广西玉林配电网的谐振过电压分析。研制出XXQ -W 1型配电网PT消谐装置动作可靠 。Based on original simulation test and simulation calculation, parametric range of resonance overvoltage due to saturated PT in distribution system was obtained. By this determined range, it can be checked that whether PT resonance will happen and how to avoid the resonance area in distribution system using the same type of PT. The test results have been used to analyze the resonance overvoltage due to saturated PT in Guangxi Yulin distribution system. Field operation shows that the developed XXQ-W1 type of PT resonance eliminator has a good effect.

关 键 词:广西玉林供电局 配电网系统 PT 谐振 过电压 铁磁谐振 消谐装置 电压互感器 

分 类 号:TM727[电气工程—电力系统及自动化] TM864

 