一起高压并联电容器装置事故分析  被引量:1

Accident Analysis of a Burnout Failure of High-Pressure Shunt Capacitor

在线阅读下载全文

作  者:陈颖 张磊 钱碧甫 张翔 CHEN Ying;ZHANG Lei;QIAN Bi-fu;ZHANG Xiang(State Grid Wenzhou Electric Power Supply Company, Wenzhou 325000, China)

机构地区:[1]国网温州供电公司,浙江温州325000

出  处:《电工电气》2016年第12期40-44,共5页Electrotechnics Electric

摘  要:特定频率的谐波下,并联电容器与系统发生并联谐振,放大谐波电流,影响电容器及系统的正常工作。分析了一起由并联电容器发生并联谐振引起的电容器组串联电抗器烧毁事故,根据对象变电站实际参数与事故现场采集数据,给出系统相应运行方式下的谐振区间,通过仿真计算阐述了电容器投切对5次谐波的放大影响,并针对该变电站的串联电抗器参数设定提出了改进措施。Under the harmonic waves of specific frequency, the parallel resonance happened between the shunt capacitor and the system, which magnified the harmonic currents and had impacts on the capacitors and the regular work of the system. This paper analyzed a burnout failure of capacitor bank series reactor caused by parallel resonance happened in the shunt capacitors. According to the actual parameters of the object transformer substation and the data collection on site of accident, this paper gave the resonance zones under different operation modes, expounded the amplification impact of capacitor switching on 5-th subharmonics and proposed the improvement measures set for series reactor parameters of this transformer substation.

关 键 词:并联电容器 串联电抗器 并联谐振 电抗率 

分 类 号:TM53[电气工程—电器]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象